40-7705I-UM Page 105 Rev 4 March 16, 2007
Fault and Status Codes (Zone information): AES Subscribers and MultiNet Receiver (not all are used by each device):
800 = No Faults, Unit OK or Restoral of all Prior Faults.
801 = Low Battery - Voltage less than 11.0V
802 = RAM Data error or RAM corrupted - Zone activation will not be reported (Sub. V1.71 &+). Reprogram Unit
803 = 7050 and 7000/2 - U11 RAM Chip Internal Battery Bad
7050E - EEPROM corrupted, or not present
804 = 7050E - A to D Converter Faulted - Zone activation will not be reported (Sub. V1.71 &+).
804 = External Device failed
805 = Modem Chip Failed or missing - U9 in 7050 and 7000/2
806 = Timing Error between CPU and Modem
807 = Ram Chip Read/Write test Failure - U11 in 7050 and 7000/2
808 = Modem Loop back Failed - U9 in 7050 and 7000/2
809 = 7050E - AC Fail or DC voltage supplied by AC has dropped below 12V
Line Card # 3 Contact ID received through IntelliTap.
Signal format: <LF>RLsACCTs18sEEEEsGGsNNNNs<CR>
See “Line card #1”, “Signal format” in “ Ademco 685 compatible output” for Key to codes used in signal format for Line Card #3 above.
This Information is passed through. Receiver number is set as programmed in the MultiNet setup. Line card is set to 3.
Line Card # 4 4+2 received through IntelliTap.
Signal format: <LF>RLsACCTsCC<CR>
CC = two digit zone code.
See “Line card #1”, “Signal format” in “ Ademco 685 compatible output” for Key to codes used in signal format for Line Card #4 above.
This Information is passed through. Receiver number is set as programmed in the MultiNet setup. Line card is set to 4.
Input Signals:
In Ademco mode the receiver will respond to 3 inputs or signals from the monitoring system.
S receiver reply will be - <LF>00sOKAYs@<CR>
<0x06> or ASCII code 6 receiver considers last message acknowledged
<0x15> or ASCII code 21 receiver will re-send last message (if not acknowledged)