40-7705I-UM Page 76 Rev 4 March 16, 2007
• Contact Debounce Time
(Loop Response) 7050 & 7750/UL only: Programs a debounce
delay for the zone inputs of 7050 and 7750/UL subscriber units to
prevent input switches or relays from causing nuisance alarms and
repeated reports of the same alarm. The default setting is 0.12
seconds. If you choose to change this setting, simply enter the new
value and press <Enter> to move to the next field. A control unit
(panel) output(s) to the 7750 RF subscriber unit shall be
programmed to latch in when it triggers a zone input on the
7750.
Note: The contact debounce time in the 7050-E, 7440, 7450, 7750-
F4x4 and 7750-F8 units are preset at 0.12 seconds and cannot be
changed.
• Acknowledgment Delay: If a subscriber unit does not receive
an acknowledgment (Packet Acknowledge) within the time
parameters set by the Acknowledgment Delay parameter, it
activates an output to annunciate the problem locally. The next
successful communication to the central station will include an
ACK Delay fault code. The default setting for this feature is 90
seconds. If you choose to change the ACKknowledgment DELAY
period, simply type in the new value. Click [OK] to complete and
send your timing parameter data.
For 7750/UL, 7750-F4x4 and 7750-F8 Subscriber Units: A
zone of the control panel shall be connected to the relay labeled
"ACK DELAY", to monitor the subscriber unit against antenna
removal, communication failure and to provide a local and remote
annunciation of such a fault condition. (Refer to subscriber
manuals.)
NOTE: For all remote program functions, watch to make sure that
a data confirmation packet is received from the target subscriber
(watch scrolling message screen area).