AES 7170 Bedienungsanleitung Seite 82

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 111
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 81
40-7705I-UM Page 82 Rev 4 March 16, 2007
Zone Configuration window for the 7050 DLR/7750 UL Bank 1 - 8
Figure 11-18
The zone configuration control block offers seven options for the
programming of each alarm zone:
Normally Open Normally Open with Restoral
Normally closed Normally Closed with Restoral
Bypassed Supervised (Not available on Bank 0, Zone 1-8)
Supervised with Restoral. (Not available on Bank 0, Zone 1-8)
Use the mouse to select the appropriate boxes for the zone you wish to
program. Banks 1-8 support Supervised programming and wiring.
UL and COMMERCIAL FIRE INSTALLATION REQUIREMENTS for
7750/UL Subscriber Units:
Zones 1-6: Bypassed
Zone 7: N.O. w/Restoral–Tamper (creates N.C. loop through zone 7 of 7072 module)
Zone 8: N.O. W/Restoral – AC Fail (from 7072 multi-board)
Refer to Subscriber Unit Manual for details on zone wiring and
programming.
Zone Configuration window for the 7050E Rev 1.8 and older
Figure 11-19
Select Bank Here
Use arrows to
scroll then click
bank number to
select.
This option row not
shown or available i
f
Bank 1 is selected
Seitenansicht 81
1 2 ... 77 78 79 80 81 82 83 84 85 86 87 ... 110 111

Kommentare zu diesen Handbüchern

Keine Kommentare