40-7705I-UM Page 15 Rev 4 March 16, 2007
Notes:
Power Line, router/ switch, and telephone connections shall not leave the
room where the AES equipment is installed. This must be accomplished
by co-locating outlets and interfacing equipment in the room where AES
equipment resides.
7705i must be installed in a UL Listed metal rack-mounting cabinet that
complies with UL864. The cabinet must be provided with integral outlets
and the ability to connect AC input via conduit. All wiring exiting the
cabinet must be in electrical conduit. Be sure non-power limited and
power limited wiring are separated by at least 1/4 inch.
All equipment shall be connected to a UL Listed UPS (UL 864) or UL
1481 power supply. In addition, the central station shall have a generator
to maintain power for the receiving equipment and environmental
controls for a period up to 24 hours or longer.
A UL Listed UPS or generator to supply 24 hours of standby must be
installed and utilized at the monitoring station. If the primary power
source at the monitoring station is lost or otherwise faulted, this condition
must be obvious to the operator on duty.
Equipment Location: A UL 7705i MultiNet Receiver must be
installed in a room where operators can properly hear the Audio Alert
Sounder.
When connecting the 7705i MultiNet Receiver’s modem to a telephone
line, a UL Listed 497A Secondary Protector is required to be installed on
the incoming lines. Installation shall be in accordance with the NEC
Article 800, the manufactures installation instructions and in accordance
with all local codes.
When connecting the 7705i MultiNet Receiver’s Ethernet ports to a
network, a UL Listed 497B Secondary Protector is required to be
installed on the Ethernet cable. Installation shall be in accordance with
the NEC Article 800, the manufactures installation instructions and in
accordance with all local codes.
4.1 Software Installation:
All necessary software is pre-installed on your 7705i.
If your system has a catastrophic failure it may require the reinstallation of the
Linux operating system and the specialized IP-Link software programs. BIOS
settings should also be checked to confirm that the unit would initialize and
operate properly. Routine backing up of the databases to another storage device
would be essential in any successful reinstallation or recovery process.
Contact AES Technical Support if you need assistance with software installation
or BIOS settings.