AES 7170 Bedienungsanleitung Seite 92

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 111
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 91
40-7705I-UM Page 92 Rev 4 March 16, 2007
12.0 Operation
This section describes two of the modes of operation your MultiNet Receiver may
be in and how to operate it.
12.1 Manual Operation
Manual operation of the MultiNet receiver is a mode where alarm and other
messages are not being sent to an Alarm Monitoring System. This would occur
when the Alarm Monitoring System was offline, down or disconnected.
Steps for Receiver operation when a MultiNet Receiver receives an alarm
message that is not being sent to an alarm automation system:
1. A waiting MultiNet Receiver receives a message from an IP-Link or detects
an off normal condition.
2. A record of the event is printed on the attached printer.
3. The Alert Sounder activates.
4. The Alert LED illuminates.
5. The message is added to the LCD queue and displayed, if it is at the top of the
queue.
6. The user may press the “Silence” button to stop the Alert Sounder.
7. The user must interpret and properly respond to the message displayed. Refer
to Appendix E for guidance with interpreting the displayed messages.
8. Once the information on the display is no longer needed, the user can press
the “Acknowledge” button to remove the message from the queue.
9. When the Acknowledge is accepted an acknowledge message is printed
indicating which of the previously printed messages is being acknowledged.
A tracking number is recorded to assist in locating it in the logs for future
review.
10. If the message is not acknowledged within 30 seconds of a Silence Button
press, the Alert Sounder is re-activated.
11. Once a message is acknowledged and removed from the queue, the next
message in the queue is annunciated and displayed as described above. If no
messages are in the queue, the MultiNet Receiver returns to its normal waiting
mode.
12.2 Automatic Operation
Automatic operation of the MultiNet receiver is a mode where alarm and other
messages are being sent to an Alarm Monitoring System. No user interaction
is required at the Receiver as long as the Alarm Monitoring System properly
acknowledges the messages.
The MultiNet receiver defaults to Manual
Operation when Alarm Automation is not in use